Can I Use Parts From Different Brands Together? - Ask The Expert Episode 284

Today's question is from Rick. "Hey Dan. Heat pump condenser 2.5 ton Goodman. Can I install it to a 3 ton Carrier air handler regular A coil evap? I don't need the heat exchanger to work. But my inside unit has a TXV. I think regular heat pump systems use fixed orifice? Thanks for your help, you are very knowledgable." If they are both using R410A, and the TXV is intended for R410A, then yes, it should work. You might want to check on the warranties though.
Comments
Leave your comment
Your email address will not be published
Heberto
Loading...
Hey Dan, I have a furnace goodman 3.5 tons evaporator coil work with r22 and r410a. I installed a condenser trane xr 16 seer 3.5tons. I want install a txv but My question is, the txv must be match with condenser or with evaporator? Thanks bro!
Rebekah Muller
Loading...
It should be matched with the condenser.